General specifications | ||
Switching element function | NAMUR, NC | |
Rated operating distance | 30 mm | |
Installation | not bdable | |
Output polarity | NAMUR | |
Assured operating distance | 0 ... 24.3 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r303 | 0.85 | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 ... 150 Hz | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Compliance with standards and directives | ||
Standard conbity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165F | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | Products with a maximum operating voltage of ≤36 V do not bear a CCC marking because they do not require approval. | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | up to 2.5 mm2 | |
Housing material | PBT | |
Sensing face | PBT | |
Protection degree | IP68 | |
General inbation | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G; 2G; 1D |