下載PDF版完整參數(shù)表:
產(chǎn)品闡述 | ||
---|---|---|
KE1 switch cabinet module 4 bs and 4 outputs |
General specifications | ||
---|---|---|
Slave type | A/B slave | |
AS-Interface specification | V3.0 | |
Required master specification | ≥ V3.0 | |
UL File Number | E87056 | |
Functional safety related beters | ||
MTTFd | 90 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Indicators/operating means | ||
LED FAULT |
error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
|
LED PWR | AS-Interface voltage; LED green | |
LED AUX |
ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED IN | switching state (b); 4 LED yellow | |
LED OUT | Switching state (output); 4 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 40 mA | |
Protection class | III | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 4 bs for 2-wire sensors (PNP), DC or for mechanical contacts | |
Supply | from external auxiliary voltage UAUX | |
Input current | ≤ 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 2 mA | |
1 (attenuated) | ≥ 4 mA | |
Signal delay | < 2 ms (b/AS-Interface) | |
Signal frequency | ≤ 250 Hz | |
Output | ||
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Current | 0.5 A per output , 2 A per module | |
Voltage | ≥ (UAUX - 0.5 V) | |
Usage category | DC-13 | |
Compliance with standards and directives | ||
Directive conbity | ||
EMC Directive 2004/108/EC | EN 50295:1999 | |
Standard conbity | ||
Noise immunity | EN 61326-1:2006 | |
Emitted interference | EN 55011:2009 | |
Input | EN 61131-2:2007 | |
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 50295:1999, IEC 62026-2:2006 | |
Programming instructions | ||
Profile | S-7.A.7 | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 7 | |
Data bits (function via AS-Interface) | b output | |
D0 | IN1 O1 | |
D1 | IN2 O2 | |
D2 | IN3 O3 | |
D3 | IN4 O4 | |
Parameter bits (programmable via AS-i) | function | |
P0 |
Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
|
P1 |
Input filter P1 = 0 b filter on, pulse suppression ≤ 2 ms P1 = 1 b filter off (default settings) |
|
P2 |
Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 90 % , noncondensing | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection |
removable spring double terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 1.5 mm2 recommended tools for 1.5 mm2: PxC CRIMPFOX ZA3 or Weidmüller PZ 6 roto |
|
Material | ||
Housing | PA 66-FR | |
Mass | 80 g | |
Mounting | DIN mounting rail |