西門子CU320控制單元6SL3040-0MA00-0AA0
型號:6SL3040-1MA00-0AA0 (西門子CU320-2DP控制單元)
參數(shù):SINAMICS CONTROL UNIT CU320-2 DP WITH PROFIBUS INTERFACE WITHOUT COMPACT FLASH CARD
聯(lián)系電話:021-60541249
手 機(jī):18621061383
CU320-2 Control Units |
CU320‑2 PN Control Unit
The communication, open-loop and closed-loop control functions for one or more Motor Modules and the Line Module are executed in a CU320‑2 Control Unit. The CU320‑2 Control Unit is essentially designed for multi-axis operation.
CU320‑2 DP Control Unit with BOP20 Basic Operator Panel
The CompactFlash card contains the firmware and beter settings. The CompactFlash card is plugged into the appropriate slot on the CU320‑2 Control Unit.
A CU320‑2 Control Unit can perb the communication, open-loop and closed-loop control functions for several Motor Modules. The computing capacity required increases in proportion to the number of connected Motor Modules and system components and in relation to the dynamic response required. For the CU320‑2 Control Unit, the perbance expansion is necessary for machines with 4 axes or more. The utilization of the CU320‑2 Control Unit can be calculated with the SIZER for Siemens Drives engineering tool.
In addition to the firmware, the CompactFlash Card also contains licensing codes which are required to enable firmware options.
In addition to the Article No., the following firmware options can currently be ordered with or without perbance expansion:
After the appropriate license has been purchased via the WEB License Manager available on the Internet, firmware options can also be subsequently enabled.
CU320‑2 Control Units feature the following interfaces as standard:
A shield connection for the signal cable shield of an option module is located on the CU320‑2 Control Unit.
The available slot is used to optionally expand the interfaces, for example, to include additional terminals or for communication purposes.
The status of the CU320‑2 Control Unit is indicated via multi-color LEDs.
As the firmware and beter settings are stored on a plug-in CompactFlash card, the Control Unit can be changed without the need for software tools.
The CU320‑2 Control Unit can be mounted on the side of the Line Module in booksize bat via brackets integrated in a Line Module. The CU320‑2 Control Unit can also be fixed to the wall of the control cabinet using the integrated fixing lugs. As the CU320‑2 Control Unit is not as deep as the Line Modules, suitable spacers are available to increase the depth of the CU320‑2 Control Unit to 270 mm (10.6 in).
DRIVE‑CLiQ components such as Motor Modules and Active Line Modules can be connected to a CU320‑2 Control Unit. The number of modules depends on the perbance required, including duty type and additional functions.
The BOP20 Basic Operator Panel can also be snapped onto the CU320‑2 Control Unit during operation to perb diagnostics.
The CU320‑2 Control Unit and other connected components are commissioned and diagnosed with the STARTER commissioning tool.
A CompactFlash card with firmware version V4.4 or higher is a mandatory requirement for operation of the CU320‑2 PN Control Unit.
A CompactFlash card with firmware version V4.3 or higher is a mandatory requirement for operation of the CU320‑2 DP Control Unit.
Connection example of a CU320‑2 Control Unit
|
CU320‑2 Control Unit |
---|---|
PROFINET |
6SL3040-1MA01-0AA0 |
Current requirement, max.
At 24 V DC, |
1.0 A |
Conductor cross-section, max. |
2.5 mm2 |
Fuse protection, max. |
20 A |
Digital bs |
In accordance with IEC 61131‑2 Type 1 12 floating digital bs 8 bidirectional non-floating digital bs/digital outputs |
|
-3 ... +30 V |
|
-3 ... +5 V |
|
15 ... 30 V |
|
3.5 mA |
|
|
|
5 μs |
|
50 μs |
|
1.5 mm2 |
Digital outputs Sustained short-circuit strength |
8 bidirectional non-floating digital bs/digital outputs |
|
24 V DC |
|
500 mA |
|
|
|
150 μs/400 μs |
|
75 μs/100 μs |
|
1.5 mm2 |
Power loss |
24 W |
PE connection |
M5 screw |
Ground connection |
M5 screw |
Dimensions |
|
|
50 mm (1.97 in) |
|
300 mm (11.81 in) |
|
226 mm (8.90 in) |
Weight, approx. |
2.3 kg (5.07 lb) |
Certificate of suitability |
cULus |