KVV控制電纜、控制電纜KVV、KVV電纜
系列代號 Series code
控制電纜control cable………………………………………………………………………………………K
阻燃系列 Flame-retardant series
阻燃A類 Flame-retardant class A…………………………………………………………………………ZA
阻燃B類Flame-retardant class B………………………………………………………………………ZB
阻燃C類Flame-retardant class C…………………………………………………………………………ZC
阻燃D類Flame-retardant class D…………………………………………………………………………ZD
耐火系列 Fire-safe series
阻燃A類耐火flame-retardant class A fire-safe…………………………………………………………ZAN
阻燃B類耐火flame-retardant class B fire-safe…………………………………………………………ZBN
阻燃C類耐火flame-retardant class C fire-safe…………………………………………………………ZCN
阻燃D類耐火flame-retardant class D fire-safe…………………………………………………………ZDN
導(dǎo)體代號Conductor code
銅導(dǎo)體(省略)Copper conductor ( omitted )………………………………………………………………T
絕緣代號Insulation code
聚氯乙烯polyvinyl chloride (PVC)insulated……………………………………………………………V
護(hù)套代號1)Sheath code
聚氯乙烯護(hù)套 polyvinyl chloride and sheath………………………………………………………………V
聚乙烯護(hù)套 polyethylene sheath……………………………………………………………………………Y
鎧裝代號Amour code
雙鋼帶鎧裝steel tape armoured ……………………………………………………………………………2
細(xì)圓鋼絲鎧裝thin steel-wire armoured ……………………………………………………………………3
外護(hù)套代號Outer sheath code
聚氯乙烯外護(hù)套 polyvinyl chloride outer sheath …………………………………………………………2
聚乙烯外護(hù)套 polyethylene outer sheath ………………………
二:KVV22控制電纜使用特性:
U0/U=450/750 V。
其中:
U0:任一主絕緣導(dǎo)體和“地”(金屬屏蔽,金屬套或周圍介質(zhì))之間的電壓有效值。
U:多芯電纜(電線)或單芯電纜(電線)系統(tǒng)任一兩相導(dǎo)體之間的電壓有效值。
2、 導(dǎo)體額定工作溫度
電纜導(dǎo)體的最高額定工作溫度為70℃。
短路時(最長持續(xù)時間不超過5s)電纜導(dǎo)體的最高溫度不超過160℃。
3、 敷設(shè)環(huán)境溫度
電纜敷設(shè)時的環(huán)境溫度應(yīng)不低于0℃,否則需要事先預(yù)熱。
4、 安裝彎曲半徑
a) 無鎧裝層的電纜,應(yīng)不小于電纜外徑的6倍;
b) 有鎧裝或銅帶屏蔽結(jié)構(gòu)的電纜,應(yīng)不小于電纜外徑的12倍;
c) 有屏蔽層結(jié)構(gòu)的軟電纜,應(yīng)不小于電纜外徑的6倍。
5、 KVV控制電纜運(yùn)輸和保管要求
電纜盤不允許平放。
運(yùn)輸中嚴(yán)禁從高處扔下裝有電纜的電纜盤,嚴(yán)禁機(jī)械損傷電纜。
電纜如果需要分段使用,電纜分段后必須用防水封帽將電纜頭密封,防止進(jìn)水。
KVV控制電纜、控制電纜KVV、KVV電纜